Electro-Air EASASD-18ASC Anleitung zur Fehlerbehebung

Stöbern Sie online oder laden Sie Anleitung zur Fehlerbehebung nach Luftfilter Electro-Air EASASD-18ASC herunter. Electro-Air EASASD-18ASC Troubleshooting guide Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 12
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
INSTALLATION, OPERATION AND
SERVICE INSTRUCTIONS
MODELS
ASAS-10ASC, ASAS-11ASC, ASAS-12ASC, ASAS-18ASC
GSAS-10ASC, GSAS-11ASC, GSAS-12ASC, GSAS-18ASC
ELECTRONIC AIR CLEANERS
IMPORTANT: PLEASE READ MANUAL BEFORE OPERATING UNIT
Features
Lifetime Filter System never needs replacing
Electronically removes dust, mites, pollen, pet dander, tobacco smoke, cooking smoke
and grease, mold, fungi, bacteria, and more down to 0.01 micron
Light Weight Aluminum Collecting Cells are durable and easy to maintain
Cell Guides ensure proper placement of collecting cells
Activated Carbon Filters remove unpleasant odors
Galvanized Steel Cabinet for solid vertical or horizontal installation
Durable Scratch-Resistant powder coat paint finish resists corrosion
Electronic Air Proving Switch for quick wiring
Dual Indicator Lights show Air Cleaner is working properly at a glance
FOR QUESTIONS REGARDING INSTALLATION, OPERATION & SERVICE,
CALL THE AIR CLEANER HOTLINE TOLL-FREE
1-800-267-8305
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - SERVICE INSTRUCTIONS

INSTALLATION, OPERATION AND SERVICE INSTRUCTIONS MODELS ASAS-10ASC, ASAS-11ASC, ASAS-12ASC, ASAS-18ASC GSAS-10ASC, GSAS-11ASC, GSAS-12ASC, GSAS-18AS

Seite 2 - CONTENTS

Replacing A Tungsten Ionizing Wire Replacement wires are cut to the correct length and have eyelets at each end for easy replacement. 1. Turn OFF pow

Seite 3

PROBLEM PROBABLE CAUSE REMEDY System fan is not on. Turn system fan on. Wiring improperly connected. Check wiring. Defective power switch.

Seite 4

GOODMAN MANUFACTURING COMPANY, L.P. 2550 North Loop West, Suite 400, Houston, Texas 77092 FOR MORE INFORMATION, CALL THE AIR CLEANER HOTLINE TOLL FRE

Seite 5

CONTENTS SAFETY CONSIDERATIONS 2 WHAT THE ELECTRONIC AIR CLEANER DOES 2 BENEFITS

Seite 6

1 Dirty Air 2 Prefilter 3 Ionizing Section COMPONENTS Cabinet: Constructed of heavy gauge galvanized steel to resist

Seite 7

UNIT A B C D E F G H ASAS-10ASC GSAS-10ASC 21 (53.0) 17 (43.5) 23 1/4 (59.0) 13 1/8 (33.5) 20 3/4 (53.0) 1 1/4 (3.0) 23 3/4 (60.5) 2 3/8 (6.0

Seite 8

Wiring Wiring should only be performed by qualified personnel only. All wiring must comply with all applicable codes and standards. The voltage of the

Seite 9 - Screwdriver

efficiency. The frequency of cleaning will vary from one house to another. On average, the cells should be cleaned every 3 months. 1. Remove access do

Seite 10 - Ionizing Bar

Replacing An Air Proving Switch (APS) Before replacing the APS, turn off the power to the Air Cleaner at the source. 1. Disconnect wiring from termi

Seite 11

Replacing The 24 V Transformer (A/ GSAS-12 and A/ GSAS-18 only) Before replacing 24 V transformer, turn off power to the Air Cleaner at the source. 1.

Seite 12 - ELECTRONIC AIR CLEANER

Testing Voltage At Cell 1. Open access door to Air Cleaner. Air Cleaner will shut off. 2. Insert a thin shafted screwdriver 2 to 3 inches into the h

Kommentare zu diesen Handbüchern

Keine Kommentare